HomeMy WebLinkAboutResolution - 796 - Authorizing Issuance of On-Sale Liquor License for Brem Corporation - 01/08/1974 CITY OF EDEN PRAIRIE
HENNEPIN COUNTY, MINNESOTA
RESOLUTION NO . 796
A RESOLUTION AUTHORIZING ISSUANCE OF AN
ON-SALE. LIQUOR LICENSE
WHEREAS , the Brem Corporation did apply for an on-sale liquor license
to be used in a facility located at 6534 Flying Cloud Drive , within the City
of Eden Prairie , and known as Eden Prairie Supper Club, Inc . and
WHEREAS , pursuant to the Ordinances of the City of Eden Prairie , said
officers of said Corporation did file the necessary application , and
WHEREAS , the application has been investigated under the direction of
Public Safety Director Jack Hacking, and
WHEREAS , the City Council did on the 11th day of December , 1973 ,
hold a public hearing on said application after due notice and publication , and
WHEREAS , no one appeared in opposition thereto , and upon the recommen-
dation of the City Manager and the Public Safety Director,
NOW , THEREFORE, Be It Resolved that an on-sale liquor license be issued
to the Brem Corporation for the calendar year 1974 subject to compliance with
the recommendations made by the Fire and Building Inspector in his memo to
the City Manager dated December 5 , 1973 .
ADOPTED by the City of Eden Prairie this 8th day of January, 1974 .
Mayor David W . Osterholt
Atte(3t: -�
S EA L
Cle k John Frane
1
JI
TO: Mr. Robert P. Heinrich, Village Manager
FROM: Ed Sherman , Fire/Building Inspector
SUBJECT: Eden House, 6534 Flying Cloud Drive
Occupancy: Assembly Building - Restaurant Bar
Group: B-3
Floor Area: 1st floor assembly - 21.78 square feet at 15 square feet per
occupant, load 145.
Basement area assembly - 1840 square feet at 15 square feet
per occupant, load 122.
The following is a list of the deficiencies found during the inspection
of the above referenced property.
First Floor.
1. Insufficient portable fire extinguishers in the kitchen. NFPA 1012.
Portable extinguishers installed in the kitchen area adjacent to cookirrg
equipment shall include a alkaline dry chemical type (sodium bicarbonate
or potassium bicarbonate base) having a rating of at least 20 BC.
2. Automatic shut off equipment required for deep fat fryers. NFPA 1033.
The operation of any extinguishing system shall automatically shut off
all sources of fuel and heat to all equipment protected by an extinguishing
system.
3. Improperly serviced fire protection equipment. NFPA 1121. An inspection
and servicing of the fire extinguishing system, by properly trained and
qualified persons shall be made at least every six months. Certificate
of inspection and maintenance performed shall be forwarded to the Fire
Inspector.
4. Improperly spaced deep fat fryers from surface flame. NFPA 1212(b) .
All fat fryers should be installed with at least a 15 inch space between
the fryer and surface flames from adjacent cooking equipment.
5. Improperly mounted fire extinguishers. NFPA 1131 - Extinguishers having.
a gross weight not exceeding 40 pounds shall be installed so that the
top of the extinguisher is not more than 5 feet above the floor. Ex-
tinguishers having a gross weight greater than 40 pounds shall be so
installed that the top of the extinguisher is not more than 3z feet
above the floor. Where they may be used by women, consideration shall
be given to mounting the extinguisher at a lower height. In no case
shall the clearance between the bottom of the extinguishers and the
floor be less than 4 inches.
6. Rodent poison in kitchen area is prohibited.
7. Improperly wired flood lights in lounge area . NEC 400-4. Flexible cord
shall not be used (1) as a substitute for the fixed wiring of a structure;
(2) where run through holes in oral 1 s, ceilings or floors; (3) where run
through dooriays , windows, or similar openings ; (4) where attached to
building surfaces; (5) where concealed behind building walls , ceilings
or floors.
8. Improperly spliced flexible cord. NEC 400-5. Flexible cord shall be
used only in continuous lenghts without splice or tap.
Mlemo to Hr. Robert P. Heinrich
Page Tiro
9. Electrical junction boxes not covered. MEC 37Q- 18(c) . All junction
boxes shall be provided with covers approved for the purpose.
10. Handrails on stairways insufficient and improper. UBC Section 3305(i) .
Stairways 'shall have handrails on each side, handrails shall be placed
not less than 30 inches nor more than 34 inches above the nosing of
treads, and ends of handrails shall be returned to the wall , or shall
terminate in newel posts or safety terminals.
11. Ventilation insufficient. UBC Section 605. All portions of Group B
Occupancies customarily used by human beings shall be provided with
light and ventilation by means of windows or skylights with an area not
less than one-eighth of the total floor area , one half of which shall
be openable, or shall be provided with artificial light and a mechanically
operated ventilation system. The mechanically operated ventilating
system shall supply a minimum of five cubic feet per minute of outside
air with a total circulated of not less than 15 cubic feet per minute
per occupant in all portions of the building and such system shall be
kept continuously in operation during such time as the building is oc-
cupied. If the velocity of the air at the register exceeds 10 feet
per second, the register shall be placed more than 8 feet above the
floor directly beneath.
12. Improper hardware on exit doors. NFFA 8-1261. An exit door from an
assembly occupancy shall not be provided with a latch or lock unless
it is panic hardware.
13. Insufficient exit signs. UBC Section 3312(b) . At every required exit
doorway, and wherever otherw-:se required to clearly indicate the direction
of egress, an exit sign with letters at least five inches (5") high
shall be provided from all areas.
14. Exit illumination required. UBC Section 3312(a) . Exits shall be illum-
inated at anytime the building is occupied with light having an intensity
of not less than one-foot candle at floor level .
Basement
1. Mechanical rooms not properly separated. UBC Section 708. Every room
containing a boiler or a central heating plant shall be separated from
the rest of the building by not less than a One-Hour Fire' Resistive
Occupancy Separation.
2. Unused openings in electric service panel . NEC 373-4. Unused openings
in cabinets shall be effectively closed to afford protection substantially
equivalent to that of the wall of the cabinet.
3. Exposed unused wires shall be removed or covered.
4. Furnace covers not installed. Furnace covers are part of the tested
assembly and must remain in place.
5. Combustible storage under stairway. UBC Section 3308(f) . There shall
be no enclosed usable space under stairways in an exit: enclosure, nor
shall the open space udder such stairways be used for any purpose.
6. Improper hardware on exit doors (See #r12, 1st floor deficiencies. )
7. Insufficient exit signs (See R 3, 1st floor deficiencies. )
8. Exit illumination required (See T-Ir'14, 1st floor deficiencies. )
9. Lampcord electrica) extention cords (See `7, 1st floor deficiencies.)
10. Compressed gas (CO") cylinders shall be chained to the wall to prevent
�. them from falling.
r,
Memo to Mr. Robert P. Heinrich
Page Three .
3: 11. Exposed electrical wires on compressors and control panels. (See
#9, 1st floor deficiencies. )
12. Improper amount of fire extinguishers . MRA 10. Fire extinguishers
shall be Installed outside mechanical room and all other locations to
provide extinguishers within a 50 foot travel distance.
13. Change in floor level for the required second means of egress. UBC
Section 3303. The floor or landing shall be level or not more than
two inches lower in exit ways. Provide a ramp at this area.
12-5-73